Thermocouple vs. Gas Solenoid Valve: What Happens When the Power Goes Out
By Fede5 min read
In short
The thermocouple in your kitchen holds the gas valve open while its flame heats it, and it doesn't need electricity. In a restaurant, that's not enough: if the power goes out, the burners stay lit but the extractor fans stop. That's what the solenoid is for, a valve that only stays open with power: without it, it shuts off the gas to the whole kitchen, and it has to be reopened by hand.
In your kitchen at home there's a part that keeps you safe even if you never notice it: the thermocouple. In a restaurant kitchen there's usually one more: the solenoid, an electric valve on the gas line. Both shut off the gas, but for different reasons, and one doesn't replace the other.
The thermocouple: why you wait with the knob pressed down
The thermocouple is that little metal rod next to the flame. Inside, it has two different metals joined at the tip. When the tip heats up, a tiny current appears between the two metals, about 25 to 35 millivolts. That current powers a magnet that holds the gas valve open.
The interesting part is that this current is enough to hold the valve open, but not to open it. That's why, when you light the oven, you're the one pressing the knob: you open the valve by hand and keep it pressed until the thermocouple heats up and the magnet can hold it on its own. I go into more detail in why you have to hold the gas oven knob down.
If the flame goes out, the tip cools down, the current stops and the valve closes. And it doesn't need power from the wall: it makes its own current from the heat of the flame. It isn't instant, though. In technicians' tests, the magnet is allowed to take up to three minutes to let go, although a minute and a half to two is normal.
What the thermocouple can't see
The thermocouple only knows one thing: whether its flame is lit. Nothing else matters to it. At home, with two or three burners, that's enough. In a restaurant, not so much.
In a commercial kitchen, the hood and the extractor fans do the job of a chimney: they carry away the smoke and the combustion gases. If the power goes out, the burners stay lit, because the thermocouple doesn't need electricity, but the extractors stop. And if the gases don't leave, they can end up drifting across the kitchen.
That's why, in the UK, the law treats a commercial kitchen's extraction as a power-operated flue and requires an interlock: a system that shuts off the gas to the appliances if the air stops moving. The British standard for gas catering appliances also requires them to be interlocked with any mechanical ventilation needed to run them safely.
The solenoid: a valve that needs power to stay open
That's what the solenoid valve, or gas safety valve, is for. It works the opposite way from a regular tap: it's designed to stay closed.
At rest, a spring keeps it shut. For gas to flow, someone has to open it by hand, and it stays open only while its coil gets power. If the power goes out, it closes quickly and everything goes off at once. And when the power comes back, it stays closed: it has to be opened by hand again, once whatever tripped it has been fixed.
Power isn't the only thing that can trigger it. In many kitchens, the valve is connected to the fire panel, the sprinklers, the power system or an emergency stop button at the kitchen door. And according to CIBSE, a British association of building services engineers, that interlock must not have any manual override.
When the power comes back
With the solenoid, things are more under control: if the power goes out, all the burners go off together. But there's a cost: when the power comes back, someone has to turn the gas back on and relight everything.
Before the gas is turned back on, some systems automatically test the pressure in the pipes and the appliance valves, to make sure none was left open.
And instead of a thermocouple, more professional equipment detects the flame another way: by ionization. A flame holds so many electrically charged particles that it lets a current through, and measuring that current tells you whether there's a flame and whether it's burning well. There's no waiting for anything to heat up. It's the same system many modern furnaces and boilers use.
So which one is better?
Neither: they do different jobs. The thermocouple looks after each burner, in case its flame goes out. The solenoid looks after the whole kitchen, in case the power goes out, the extractor stops or the fire alarm goes off. That's why, in a commercial kitchen, they work together.
Frequently asked questions
What is a thermocouple?
It's the little metal rod next to the flame in ovens and burners. It has two different metals joined at the tip: when it heats up, it generates a current of about 25 to 35 millivolts that holds the gas valve open.
Does a thermocouple work during a power outage?
Yes. It doesn't use household electricity: it generates its own current from the heat of the flame. That's why the oven or burner stays lit if the power goes out.
What is a gas solenoid valve?
It's an electric safety valve that a spring keeps closed at rest. It's opened by hand and stays open only while its coil gets power: if the power goes out, it closes quickly.
What happens to the solenoid valve when the power comes back?
It stays closed. Someone has to open it by hand again, once whatever tripped it has been fixed, and relight the burners.
Why does a restaurant kitchen shut off the gas if the extractor fans stop?
Because the hood and extractor fans do the job of a chimney. In the UK, the law requires a system that shuts off the gas if the air stops moving, so combustion gases don't drift across the kitchen.
Sources
The facts in this post come from these sources (checked when it was written).
- Thermocouple — Wikipedia
- Thermocouple testing procedure — HeatingHelp
- Oven thermocouple: how it works — Cooker Spare Parts
- Module 17: Commercial kitchen design for safety and energy efficiency — CIBSE Journal
- Electroválvula de seguridad gas, normalmente cerrada de rearme manual (serie EVRM-NC) — Fantini Cosmi
- Gas Check Pressure Proving System — Techrite Controls
- Flame detector — Wikipedia